MIL-DTL-3432J
c. Speed shall be adjusted to ensure that contact is maintained for at least 0.25 seconds between the electrode
and any point on the insulation or according to the formula in method 900 of UL 1581.
d. The frequency of the voltage shall be 60Hz or 400Hz, or as listed in UL 1581.
e. Use of voltmeter-equipped spark testers is optional.
f. Spark test voltage shall be in accordance with table XVII.
TABLE XVII. Spark and dielectric withstanding test voltage.
All insulation materials
Specified nominal
Spark test voltage
Specified nominal
Dielectric
thickness inclusive
(volts rms)
thickness inclusive
withstand
Inch (mm)
inch (mm)
voltage (volts)
0 to .029
1,000
3,000
0 to .020
(0 to .74)
(0 to .51)
.030 to .044
1,500
6,000
.021 to .031
(.764 to 1.12)
(.53 to .79)
.045 to .059
3,000
7,000
.032 to .047
(1.14 to 1.50)
(.81 to 1.20)
.060 and up
3,500
10,000
.048 to .063
(1.52 and up)
(1.22 to 1.60)
4,000
.064 to .077
(1.63 to 1.96)
5,000
.078 to .094
(1.98 to 2.39)
22