MIL-DTL-3849C
TABLE III. Group A inspection.
Inspection
Requirement
Verification paragraph
Materials
3.3
4.4
Visual and dimensional
3.1, 3.8
4.6.1
Workmanship
3.8
4.6.1
Construction
3.1
4.6.1
Insulation wall thickness
3.3.3.1
4.6.1
Diameter of insulated conductors
3.3.3.2
4.6.1
Insulation color coding
3.3.3.3
4.6.1
Jacket wall thickness
3.3.4.1
4.6.1
Outside diameter (cable)
3.4
4.6.1
Electrical
Dielectric withstanding voltage
3.6.1
4.6.2.1
Insulation resistance
3.6.2
4.6.2.2
Continuity
3.6.3
4.6.2.3
DC resistance
3.6.4
4.6.2.4
4.5.3 Group B inspection. Group B inspection shall consist of the inspections in table IV conducted
on a sampling basis in accordance with 4.5.4.
Table IV. Group B inspection.
Inspection
Requirement
Verification
Breaking load
3.7.1, 3.7.1.1
4.6.3.1
Staycord breaking load
3.7.1.1
4.6.3.1
Cold bend
3.7.2
4.6.3.2
Visual examination
Sea-water resistance
3.7.3
4.6.3.3
Visual examination
4.5.4 Sampling.
4.5.4.1 Lot. A lot shall consist of all cable of a single cable designation offered for inspection at one
time, except that the lot shall not exceed 1,000,000 feet (304.8 km) or one week's production, whichever
is less. The lot size shall be expressed in units of thousands of feet (total footage in lot divided by 1,000).
4.5.4.2 Sample. A sample shall consist of individual lengths of cable chosen at random from any one
lot for the purpose of inspection or test
4.5.4.3 Sample size. The sample size to be chosen from each lot shall be determined by the
applicable test method.
4.5.4.4 Specimen length. Unless otherwise specified herein, the specimen shall be of the length of
cord specified in the applicable test method.
4.5.4.5 Sample unit. A sample unit shall consist of one of the individual lengths of the sample.
4.5.4.6 Specimen. A specimen shall consist of the portion of one sample unit upon which a particular
inspection or test is to be made.