TABLE VII. Group A inspection.
Test
Requirement paragraph
Test paragraph
Visual and dimensional
Conductor
Color code
Shields
Cabling
Markings
Size and weight
Workmanship
Electrical
Conductor resistance
Voltage test (cable)
Insulation resistance
Voltage test (insulated conductors)
Shielded jacket
4.6.3 Group B inspection. Group B inspection shall consist of the tests specified in table VIII. The inspector
shall choose not less that one but not more than three sets of samples from each lot submitted for group B
inspection. Lot size for group B inspection shall be not more than 1000 lbs. for coating tests. Lot sizes for
finished cable shall be limited to 25,000 feet. When specifically requested by the procuring activity, group B
inspection may be omitted on orders of 1000 ft or less, provided the particular cable type has previously been
manufactured and tested by the manufacturer and data is on file.
TABLE VIII. Group B inspection.
Test
Requirement paragraph
Test paragraph
Conductor
Coating
Elongation of strands
Insulation
Physical properties
Coding material
Stripe durability
Stripe conductivity
Sheath
Physical properties
Marking durability
Cable
Ozone resistance
Mechanical tests
Cold bend
Capacitance
Attenuation
Impedance
4.6.4 Group C inspection. Group C inspection shall consist of the tests specified in table IX. One sample shall
be selected per each 100,000 feet of cable or fraction thereof, not to exceed a total of five samples per order.
Samples shall be selected periodically through the life of the contract to assure representative results.