MIL-DTL-13777/4C
TABLE II. Design data.
Design data
Type designation
211055
211115S
Figure number
1
2
Total wires
21
21
Number of conductors & AWG #
15/#18
6/#12
5/#18S
10/#18
6/#12
Insulation
Minimum average thickness
0.015"
0.020"
0.015"
0.020"
Spark test voltage
3000
4000
3000
4000
Inspection test voltage
1500
2000
1500
2000
Cabling
Layer 1
Filler
Filler
Layer 2
(a) Number of wires
6
6
(b) AWG #
#12
#12
(c) Maximum lay
4.00"
4.00"
Layer 3
(a) Number of wires
15
5
10
(b) AWG #
#18
#18S
#18
(c) Maximum lay
7.00"
7.00"
Sheath
Number of layers
2
2
Total thickness minimum
0.120"
0.120"
Minimum OD cable
1.040"
1.100"
Maximum OD cable
1.070"
1.130"
Maximum weight (lbs./1000ft.)
708
791
See notes at end of table.