MIL-DTL-13777/1C
TABLE III. Design data Continued.
Type designation
041260
041335
041488
Figure number
3
3
3
Total wires
4
4
4
Number of conductors & AWG #
3/#4
1/#8
4/#4
3/#2
1/#8
Insulation
Min. average thickness
0.060"
0.060"
0.078"
0.060"
Spark test voltage
5000
4000
5000
Inspection test voltage
2500
2000
2500
Cabling
Layer 1
Filler
Filler
Filler
Layer 2
(a) Number of wires
4
4
4
(b) AWG #
3/#4
1/#8
#4
3/#2
1/#8
(c) Maximum lay
8.00"
10.00"
10.75"
Sheath
Number of layers
2
2
2
Total thickness min
0.156"
0.156"
0.172"
Minimum OD cable
1.235"
1.310"
1.443"
Maximum OD cable
1.285"
1.360"
1.533"
Type designation
041635
041655
041754
Figure number
3
3
3
Total wires
4
4
4
Number. of conductors & AWG #
4/#2
3/#0
1/#8
3 #2/0
1/#4
Insulation
Min average thickness
0.075"
0.075"
0.060"
0.052"
0.032"
Spark test voltage
7500
7500
5000
7500
Inspection test voltage
5000
5000
2500
2500
Cabling
Layer 1
Filler
Filler
Filler
Layer 2
(a) Number of wires
4
4
4
(b) AWG #
1/#2
3/#0
1/#8
3 #2/0
#4
(c) Maximum lay
10.00"
12.00"
Sheath
Number. of layers
2
2
2
Total thickness min
0.188"
0.172"
0.127"
Minimum OD cable
1.610"
1.605"
1.719"
Maximum OD cable
1.660"
1.705"
1.789"
See notes at the end of table.