MIL-DTL-13777/1C
TABLE III. Design data Continued.
Type designation
030575S
030635
030675
030945
031115
Figure number
2
2
2
2
2
Total wires
3
3
3
3
3
Number of conductors & AWG #
3/#18S
3/#12
3/#10
3/#8
3/#6
Insulation
Min average thickness
0.015"
0.030"
0.030"
0.060"
0.060"
Spark test voltage
3000
4000
4000
7500
7500
Inspection test voltage
1500
2000
2000
2500
2500
Cabling
Layer 1
Filler
Filler
Filler
Filler
Filler
Layer 2
(a) Number of wires
3
3
3
3
3
(b) AWG #
#18S
#12
#10
#8
#6
(c) Maximum lay
4.00"
4.00"
4.00"
6.00"
6.00"
Sheath
Number of layers
1
1
1
1
2
Total thickness min
0.078"
0.084"
0.078"
0.090"
0.125"
Minimum OD cable
0.550"
0.620"
0.660"
0.930"
1.100"
Maximum OD cable
0.600"
0.650"
0.690"
0.960"
1.130"
Maximum Wt. (lbs./1000ft.)
253
570
710
Design data
Type designation
S031170
031355
S031640
040440
040470
Figure number
2
2
2
3
3
Total wires
3
3
3
4
4
No. of conductors & AWG #
3/#4
3/#1
3/#0
4/#20
4/#18
Insulation
Min average thickness
0.060"
0.070"
0.075"
0.015"
0.015"
Spark test voltage
7500
7500
7500
3000
3000
Inspection test voltage
2500
2500
2500
1500
1500
Cabling
Layer 1
Filler
Filler
Filler
Filler
Layer 2
(a) Number of wires
3
3
3
4
4
(b) AWG #
#4
#1
#0
#20
#18
(c) Maximum lay
1/
Sheath
Number of layers
2
1
2
1
1
Total thickness min
0.100"
0.090"
0.120"
0.070"
0.070"
Minimum OD cable
1.155"
1.340"
1.625"
0.425"
0.440"
Maximum OD cable
1.185"
1.370"
1.655"
0.455"
0.500"
Maximum Wt.(lbs./1000ft.)
1600
See notes at the end of table.