TABLE II-B. Details of aluminum conductors.
Nominal
Allowable
Stranding
Max
Conductor area
Diameter
Size
dia. of
no. of
(no. of
resistance
(circular mils)
Tensile Elongation
individual
missing
strands X
(ohms per
desig-
(KSI)
(% min)
Nominal
Min
Max
nation
strands
strands
1000
AWG of
Minimum
1/
(Inch)
(Inch)
(Inch) 1/
(Max)
@ 20 °C)
strands)
8
16,564
15,571
41x24
0
0.0201
0.150
0.160
1.093
23 - 35
1
6
28,280
26,891
70x24
0
0.0201
0.201
0.211
0.641
23 - 35
1
4
43,229
41,105
107x24
0
0.0201
0.248
0.262
0.427
23 - 35
1
2
67,874
63,771
168x24
2
0.0201
0.315
0.330
0.268
23 - 35
1
1
88,478
83,363
219x24
2
0.0201
0.353
0.368
0.214
23 - 35
1
01
104,639
98,345
259x24
3
0.0201
0.400
0.418
0.169
23 - 35
1
02
134,939
127,157
334x24
3
0.0201
0.454
0.478
0.133
23 - 35
1
03
172,512
162,500
427x24
4
0.0201
0.511
0.535
0.109
23 - 35
1
04
211,297
198,995
523x24
5
0.0201
0.563
0.587
0.085
23 - 35
1
1/ Nominal values are for information only. Nominal values are not requirements.