INCH-POUND
MIL-DTL-24643/18F
1 October 2009
SUPERSEDING
MIL-DTL-24643/18E
22 August 2002
DETAIL SPECIFICATION SHEET
CABLE, ELECTRICAL, -20 °C TO +105 °C, 1000 VOLTS, TYPE LSMSCU
(INCLUDING VARIATION LSMSCS)
This specification is approved for use by all Departments and Agencies of the Department of Defense.
The requirements for acquiring the product described herein shall consist of this specification sheet and
MIL-DTL-24643.
Construction, Watertight with Circuit Integrity
First
Copper conductor, coated or uncoated, 18 AWG, Class B stranding.
-
Second
Thermoset insulation. Minimum average wall thickness of 0.018 inch. Diameter of the
-
insulation 0.084 inch minimum.
Third
Optional glass braid.
-
Fourth
Optional covering (unless required by 3.3.5 of MIL-DTL-24643). Diameter over the
-
glass braid covering shall be a maximum of 0.113 inch. Standard identification code
applied by Method 1.
Fifth
-
accordance with 3.4.4 of MIL-DTL-24643. Except the lay of the two outer layers for
sizes 44, 61, and 91 shall not exceed 18 times the pitch diameter of the layer. Cabling
sequence shall be consecutive, starting with no. 1 from the center outward. Fillers may
be used as necessary to form a firm well-rounded assembly.
Sixth
An optional binder.
-
Construction, Variant Type LSMSCU
Seventh
-
Construction, Variant Type LSMSCS
Seventh
Braided shield of tin-coated copper.
-
Eighth
Spirally wrapped polyethylene terephthalate (polyester film) separator tape.
-
Ninth
Braided shield of tin-coated copper.
-
Tenth
An optional binder.
-
Eleventh
-
AMSC N/A