MIL-DTL-3432J
APPENDIX B
TABLE B-II. Insulation for cables rated 0 through 2000 volts physical and aging requirements.
Physical Requirements
Tensile strength, minimum
1800 psi, 12.5 MPa
Elongation at rupture, minimum %
250
Aging Requirements
After Air Oven Test @ 121°C + 1°C for 168 hours
Tensile Strength and Elongation at Rupture, Minimum % of Unaged Value
75
After Hot Creep Test at 150°C ± 2°C, Filled
Hot Creep Elongation, Maximum % 1/
175
Hot Creep Set, Maximum % 1/
10
After Hot Creep Test at 150°C± 2°C, Unfilled
Hot Creep Elongation, Maximum % 1/
100
Hot Creep Set, Maximum % 1/
5
1/ If this value is exceeded, the solvent exception test may be performed and will serve as a referee method to
determine compliance (maximum percent after 20 hours drying time 30).