INCH-POUND
MIL-DTL-24643/8E
1 October 2009
SUPERSEDING
MIL-DTL-24643/8D
22 August 2002
DETAIL SPECIFICATION SHEET
CABLE, ELECTRICAL, -20 °C TO +90 °C, 300 VOLTS, TYPE LSMMOP
This specification is approved for use by all Departments and Agencies of the Department of Defense.
The requirements for acquiring the product described herein shall consist of this specification sheet and
MIL-DTL-24643.
Construction, Non-Watertight
First
Copper conductor, coated or uncoated, 24 AWG, Class O stranding.
-
Second
Separator may be used at manufacturer's option where required to provide free-stripping
-
insulation.
Third
Thermoset insulation. Minimum average wall thickness of 0.020 inch. Standard
-
identification code applied by Method 1 or Method 3. If identification Method 1 is used,
the insulation color shall be black.
Fourth
Five conductors shall be cabled together with a left-hand lay as required for the
-
completed cable to meet the twisting and bending endurance tests. A tie cord shall be
laid straight as a central core. Fillers may be used as necessary to form a firm well-
rounded assembly. Cabling sequence shall be consecutive.
Fifth
An optional binder.
-
Sixth
Cross-linked polyolefin jacket. Minimum average wall thickness of 0.040 inch.
-
AMSC N/A
FSC 6145