INCH-POUND
MIL-DTL-24643/7F
1 October 2009
SUPERSEDING
MIL-DTL-24643/7E
22 August 2002
DETAIL SPECIFICATION SHEET
CABLE, ELECTRICAL, -20 °C TO +90 °C, 600 VOLTS, TYPE LSMHOF
This specification is approved for use by all Departments and Agencies of the Department of Defense.
The requirements for acquiring the product described herein shall consist of this specification sheet and
MIL-DTL-24643.
Construction, Non-Watertight
First
Copper conductor, coated or uncoated, 16 AWG, Class K stranding.
-
Second
Separator may be used at manufacturer's option where required to provide free-stripping
-
insulation.
Third
Thermoset insulation. Minimum average wall thickness of 0.020 inch. Standard
-
identification code applied by Method 1 or Method 3. If identification Method 1 is used,
insulation color shall be black.
The specified number of conductors (see table I) shall be cabled together as required for
Fourth
-
the completed cable to meet the twisting and bending endurance tests. The outer layer
shall be a left-hand lay. The inner layer(s) lay direction at the manufacturer's option.
Fillers may be used as necessary to form a firm well-rounded assembly. Cabling
sequence to be consecutive, starting with no. 1, from the center outward. A single
conductor shall not be used in the center for the cable core.
Fifth
An optional binder.
-
Sixth
Cross-linked polyolefin jacket. Minimum average wall thickness of 0.060 inch
-
AMSC N/A
FSC 6145
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business