MIL-DTL-24643/38F
Qualification Inspection:
Qualification inspection shall include basic electricals; groups A, B, C, and D; plus the following:
Aging and compatibility (cable) (125±5 °C)
No failure
Abrasion resistance (jacket) (scrapes, min.)
75
Acid gas equivalent (percent, max.)
Jacket
2
Fillers
2
Insulation
18
Shield insulation /group covering
2
Halogen content (percent, max.)
Jacket
0.2
Fillers
0.2
Insulation
0.2
Immersion (jacket)
Tensile strength (percent of unaged, min.)
50
Elongation (percent of unaged, min.)
50
Smoke index (max.)
Jacket
25
Fillers
45
Insulation
45
Toxicity index (max.)
Jacket
5
Fillers
5
Insulation
1.5
Durometer (jacket) - Type A (hardness, min.)
80
Weathering (jacket)
No failure
Electrical moisture absorption
No failure
UNIT ORDERING LENGTHS:
Type
Feet (nominal)
LSECM
1000
CHANGES FROM PREVIOUS ISSUE: Marginal notations are not used in this revision to identify changes with
respect to the previous issue due to the extent of the changes.
4