MIL-DTL-24643/24C
Insulation
50
Jacket (when tested at 200 °C)
50
Physicals (unaged)
Insulation (extruded)
Tensile strength (lb/in2, min.)
700
Elongation (percent, min.)
150
Jacket (cable)
Tensile strength (lb/in2, min.)
800
Elongation (percent, min.)
250
Durometer (jacket) - Type A (hardness, min.)
60
Group C:
Physicals, cable aging (260±10 °C)
Jacket (cable)
Tensile strength (lb/in2, min.)
600
Elongation (percent, min.)
150
Group D:
Flame propagation (cable)
No failure
Qualification Inspection:
Qualification inspection shall include basic electricals; groups A, B, C, and D; plus the following:
Gas flame (3 hours)
No failure
Aging and compatibility (cable) (125±5 °C)
No failure
Armor (conformance to material, construction and coverage)
No failure
Acid gas equivalent (percent, max.)
Jacket
2
Fillers
2
Insulation
18
Halogen content (percent, max.)
Jacket
0.2
Fillers
0.2
Insulation
0.2
Smoke index (max.)
Jacket
35
Fillers
45
4