MIL-DTL-24643/13E
Maximum
90
Group B:
Thermoset proof test (percent, max.)
Insulation
50
Jacket (when tested at 200 °C)
50
Twisting and bending endurance (see table I for roller size)
At 75 °C (cycles, min.)
6000
At minus 30±2°C (cycles, min.)
2000
Physicals (unaged)
Insulation (extruded)
Tensile strength (lb/in2, min.)
700
Elongation (percent, min.)
150
Jacket (cable)
Tensile strength (lb/in2, min.)
1300
Elongation (percent, min.)
160
Tear (lb/in thickness, min.)
35
Group C:
Physicals (aged) air oven
Insulation (extruded)
Tensile strength (percent of unaged, min.)
75
Elongation (percent of unaged, min.)
75
Jacket (cable)
Tensile strength (percent of unaged, min.)
60
Elongation (percent of unaged, min.)
60
Permanence of printing (jacket) (cycles, min.)
125
Heat distortion (percent of unaged, max.)
30
Shrinkage
No failure
Shield - conformance to material, construction and coverage
No failure
Group D:
Flame propagation (cable)
No failure
Qualification Inspection:
Qualification inspection shall include basic electricals; groups A, B, C, and D; plus the following:
Aging and compatibility (cable) (125±5°C)
No failure
3
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business