INCH-POUND
MIL-DTL-24643/11E
1 October 2009
SUPERSEDING
MIL-DTL-24643/11D
22 August 2002
DETAIL SPECIFICATION SHEET
CABLE, ELECTRICAL, -20 °C TO +90 °C, 600 VOLTS, TYPE LSSSF
This specification is approved for use by all Departments and Agencies of the Department of Defense.
The requirements for acquiring the product described herein shall consist of this specification sheet and
MIL-DTL-24643.
Construction, Non-Watertight
First
Copper conductor, uncoated, 300 MCM AWG, Class G stranding (see note 1).
-
Second
Separator may be used at manufacturer's option where required to provide free-stripping
-
insulation.
Third
Thermoset insulation. Minimum average wall thickness of 0.075 inch.
-
Fourth
Optional reinforcement.
-
Fifth
Cross-linked polyolefin jacket bonded to the underlying insulation. Minimum average
-
wall thickness of 0.075 inch.
NOTE: The copper shall be hard drawn, having a minimum tensile strength of 67,200 lb/in, and minimum
elongation of 0.85 percent in 60-inch lengths before stranding. The resistance specified is based on
102.7 percent of the values required for annealed bare copper.