MIL-DTL-24640/15E
Acid gas equivalent (percent, max.)
Jacket
2
Fillers
2
Insulation
18
Halogen content (percent, max.)
Jacket
0.2
Fillers
0.2
Immersion (jacket)
Tensile strength (percent of unaged, min.)
50
Elongation (percent of unaged min.)
50
Smoke index (max.)
Jacket
25
Fillers
45
Insulation
10
Toxicity index (max.)
Jacket
5
Fillers
5
Insulation
1.5
Durometer (jacket) - Type A (hardness, min.)
80
Weathering (jacket)
No failure
Fungus resistance
No failure
Abrasion resistance
No failure
Gas flame (3 hour)
Not applicable
Component wire
No failure
UNIT ORDERING LENGTHS:
Type and size
Feet (nominal)
3 & 14
500
2XSAW-3, 2XSAW-7, 2XSAW-14,
2XSAOW-3, 2XSAOW-7, 2XSAOW-10,
19 - 37
250
2XSAOW-14, 2XSAOW-19, 2XSAOW-
24, 2XSAOW-30, 2XSAOW-37
CHANGES FROM PREVIOUS ISSUE: Marginal notations are not used in this revision to identify changes with
respect to the previous issue due to the extent of the changes.