Dry arc propagation resistance (Test required for initial qualification only): Test in accordance with MIL-STD-2223
Method 3007. Measure the damage of the bundle along the axis. The wire is acceptable if the following criteria are
met:
1. A minimum of 67 wires pass the dielectric test.
2. Three wires or less fail the dielectric test in any one bundle.
3. Actual damage to the wire is not more than 3 inches in any test bundle.
Blocking: 260°C ± 2°C (500°F ± 3.6°F)
Color: In accordance with MIL-STD-104, class 1; except as noted below. White preferred. Conformity of color to
the limits of MIL-STD-104 shall not be required after oven exposure.
Munsell color limits for UV laser markable wire
Value
Chroma
Color
Hue
From
To
From
To
From
To
N/A
N/A
7
8.5
2.5RN
2.5RN
Black
4
6
7
8
5PB
7.5B
Blue
2
6
7
9
2.5G
7.5G
Green
4
6
7
8
10RP
5R
Red
4
6
8
9
5Y
10Y
Yellow
2
4
7
9
2.5YR
7.5R
Brown
8
10
6
7
10R
2.5YR
Orange
4
8
7
8
2.5P
7.5R
Violet
Same as Black
Same as Black
Same as Black
Gray
Color striping or banding durability: 125 cycles (250 strokes), 250 grams weight
Conductor strand adhesion: Not required
Continuous lengths: Schedule B
Dynamic cut- through (Test required for initial qualification only): Test in accordance with ASTM D 3032,
Section 22. Blade shall be the standard cutting blade except the cutting edge radius shall be 0.005 ± 0.001 inch.
Minimum average dynamic cut - through (lbs) shall be as follows:
23±5°C
150±5°C
200±5°C
260±5°C
Wire Size
26
10 lbs.
8 lbs.
6 lbs.
4 lbs.
20
25 lbs.
20 lbs.
15 lbs.
10 lbs.
16
25 lbs.
20 lbs.
15 lbs.
10 lbs.
Flammability: Test in accordance with MIL-STD-2223, Method 1006, Procedure A.
Requirements:
Duration of after - flame 3 seconds (max)
Flame travel
3.0 inches (max)
No flaming of tissue
Forced Hydrolysis: (Test required for initial qualification only) 2000 hours at 70°C. Test 5 samples of AWG size
20 only in accordance with SAE AS4373 method 602. All 5 samples must pass the dielectric test as listed in method
602.