MIL-DTL-13273C
insulating, the elongation of individual strands shall be not less than 5%, and the tensile strength shall not
exceed 58,000 psi.
3.4 Insulation. The stranded conductors shall be insulated with a natural rubber compound capable
of meeting the requirements specified herein.
3.4.1 Colors. The color of the insulation on the two conductors of the two conductor cord shall be
black and white, respectively. The color of the insulation on the three conductors of the three conductor
cord shall be black, white and red, respectively. The color of the insulation on the four conductors of the
four conductor cord shall be black, white, red, and green respectively.
3.4.2 Sunproofing wax. The Buna S insulating compound shall contain not less than 2.5 pounds of
approved sunproofing wax per 100 pounds of Buna S in the finished insulating compound.
3.4.3 Dimensions. The diameter of the insulated conductor shall not exceed 0.080 inch (2.03 mm),
and the minimum wall thickness at any point shall be not less than 0.010 inch (.25 mm).
3.4.4 Physical properties. The insulating compound shall conform to the following physical
requirements before and after aging:
Unaged:
Tensile strength, minimum, psi.
600
Elongation, minimum, percent
250
Set, maximum inch
0.5
After 96 hours aging in oxygen bomb at 70± 1°C
Tensile strength, minimum, psi.
450
Elongation, minimum, percent
175
The insulation shall be capable of stripping freely from the conductor. The compound used shall contain
not more that 0.5% of free sulfur after vulcanization.
3.5 Cabling. The insulated conductors shall be cabled together with a right hand lay of twist not
greater than 1.5 inches (38.10 mm).
3.6 Jacket. The cabled conductors shall be jacketed with a smooth dense, Buna S compound or
Buna S, natural rubber blend compound. The amount of natural rubber in the jacket compound shall not
exceed 25% by weight of the total Buna S and natural rubber in the compound. The jacketing compound
shall contain not less than 4 pounds of an approved type of sunproofing wax per 100 pounds of the total
of Buna S and natural rubber in the jacket compound after vulcanization into the construction, the
average diameter of the 2-conductor cord shall be 0.220 inch (5.59 mm) ± 0.010 inch (.25 mm), and the
average diameter of the 3 and 4-conductor cordage shall be 0.250 inch (6.35 mm) ± .010 inch (.25 mm).
The average diameter shall be taken as the mean of the maximum and minimum diameter in any cross-
section of the straight length of cord. The jacket thickness at any cross-section of cord shall be not less
than 0.010 inch. (.25 mm) The minimum jacket thickness on the straight portion of the cord shall be
0.020 inch (.51 mm). The jacket shall be free stripping from the insulation.
3.6.1 Jacket physical properties. After vulcanization, the jacket shall have the following physical
properties measured on straight portions of the cord.
3.6.1.1 Jacket physical properties before aging. The tensile strength of the jacket shall be not less
than 1200 psi. The jacket elongation shall be not less than 175%.
3