MIL-DTL-24643/50E
TABLE I. Details.
Overall diameter
Insulation
Cable jacket
Military part no.
AWG
thickness min.
thickness min.
Type and size
min.
max.
M24643/50
conductor size
avg. (inch)
avg. (inch)
(inch)
(inch)
-01UN
LSFNW-3
16 (Class B)
0.030
0.040
0.413
0.447
-02UN
LSFNW-4
14 (Class B)
0.030
0.040
0.475
0.513
-03UN
LSFNW-9
10 (Class B)
0.030
0.040
0.583
0.630
-04UN
LSFNW-23
7 (Class B)
0.045
0.055
0.768
0.830
-05UN
LSFNW-50
3 (Class C)
0.062
0.055
1.016
1.050
-06UN
LSFNW-75
1 (Class C)
0.062
0.065
1.206
1.240
-07UN
LSFNW-100
0 (Class D)
0.062
0.065
1.324
1.385
-08UN
LSFNW-150
000 (Class D)
0.062
0.065
1.591
1.625
-09UN
LSFNW-200
0000 (Class D)
0.072
0.065
1.786
1.820
TABLE II. Electrical details.
Insulation
Accelerated service
Conductor
Voltage withstand
resistance
Type and size
loading current
resistance (ohms)
min. (volts)
(megohms)
(amperes)
LSFNW-3
4.3
6000
4000
N/A
LSFNW-4
2.68
5000
4000
N/A
LSFNW-9
1.08
3800
4000
N/A
LSFNW-23
0.543
3700
5500
115
LSFNW-50
0.210
3000
6000
215
LSFNW-75
0.134
3000
6000
285
LSFNW-100
0.106
2500
6000
335
LSFNW-150
0.0674
2500
6000
440
LSFNW-200
0.0536
2000
6500
525
REQUIREMENTS:
Qualification required.
INSPECTION:
Basic Electricals:
Conductor resistance (ohms/1000 feet at 25 °C, max.)
See table II
Voltage withstand (volts, root mean square, min.)
Conductor to conductor
See table II
Insulation resistance (megohms/1000 feet, min.)
Conductor to conductor
See table II
Conductor continuity
No failure
2
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business