MIL-DTL-24640/6E
Jacket
2
Fillers
2
Insulation
18
Halogen content (percent, max.)
Jacket
0.2
Fillers
0.2
Immersion (jacket)
Tensile strength (percent of unaged, min.)
50
Elongation (percent of unaged, min.)
50
Smoke index (max.)
Jacket
25
Fillers
45
Insulation
10
Toxicity index (max.)
Jacket
5
Fillers
5
Insulation
1.5
Durometer (jacket) - Type A (hardness, min.)
80
Weathering (jacket)
No failure
Fungus resistance
No failure
Abrasion resistance
No failure
Gas flame (3 hour)
Not applicable
Component wire
No failure
UNIT ORDERING LENGTHS:
Type and size
Feet (nominal)
All types and sizes 2 - 10
500
All types and sizes 18 - 40
250
CHANGES FROM PREVIOUS ISSUE: Marginal notations are not used in this revision to identify changes with
respect to the previous issue due to the extent of the changes.
5
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business